; GSD-Datei fuer PROFIBUS-DP Koppler/SPC3
; Hersteller: Beckhoff Automation GmbH
; Eiserstr. 5
; 33415 Verl
; Tel.: +49(0)5246/963-0
; Best.-Nr.: IP23xx-B310,IP24xx-B310
; Stand : 06.02.06
;
;
;----------------------- TwinCAT ----------------------
;
Tc_KBus_supp = 1 ; Buskoppler
Tc_Plc_supp = 0 ; Bus-Controller
Tc_Fbb_supp = 1 ; Feldbus Box
Tc_Firmware_Flashable = 1 ;
Tc_Valid_Term(0) = 1677723900 ; 0x64000000 + 2300
Tc_Valid_Term(1) = 1677723901 ; 0x64000000 + 2301
Tc_Valid_Term(2) = 1677723902 ; 0x64000000 + 2302
Tc_Valid_Term(3) = 1677723910 ; 0x64000000 + 2310
Tc_Valid_Term(4) = 1677723911 ; 0x64000000 + 2311
Tc_Valid_Term(5) = 1677723912 ; 0x64000000 + 2312
Tc_Valid_Term(6) = 1677723920 ; 0x64000000 + 2320
Tc_Valid_Term(7) = 1677723921 ; 0x64000000 + 2321
Tc_Valid_Term(8) = 1677723922 ; 0x64000000 + 2322
Tc_Valid_Term(9) = 1677723930 ; 0x64000000 + 2330
Tc_Valid_Term(10) = 1677723931 ; 0x64000000 + 2331
Tc_Valid_Term(11) = 1677723932 ; 0x64000000 + 2332
Tc_Valid_Term(12) = 1677724000 ; 0x64000000 + 2400
Tc_Valid_Term(13) = 1677724001 ; 0x64000000 + 2401
Tc_Comment = "Digitale In/Output Kompakt Box"
Tc_BitmapFile = "Ip.bmp"
Tc_VendorBitmapFile = "Beckhoff.bmp"
;
;------------------------- DP -------------------------
;
#Profibus_DP
;
;------------------ PrmText-Definitionen --------------
;
PrmText = 1
Text(0) = "ist nicht aktiv"
Text(1) = "ist aktiv"
EndPrmText
PrmText = 12
Text(0) = "synchron"
Text(1) = "freilaufend"
EndPrmText
PrmText = 13
Text(0) = "Zyklus wird gestoppt"
Text(1) = "Outputs werden 0"
Text(2) = "Outputs bleiben gleich"
EndPrmText
;
;------------- ExtUserPrmData-Definitionen --------------
;
ExtUserPrmData = 12 "Prozessabbildaktualisierung"
Bit(6) 1 0-1
Prm_Text_Ref = 12
EndExtUserPrmData
ExtUserPrmData = 13 "Reaktion auf DP-Fehler"
BitArea(0-1) 0 0-2
Prm_Text_Ref = 13
EndExtUserPrmData
ExtUserPrmData = 86 "Fast FreeRun-Mode"
Bit(4) 0 0-1
Prm_Text_Ref = 1
EndExtUserPrmData
;
;---------------------- DP-General ---------------------
;
GSD_Revision = 2
Vendor_Name = "BECKHOFF"
Model_Name = "IP23xx-B3xx/IP24xx-B3xx"
Revision = "Revision 3.2"
Ident_Number = 0x0515
Protocol_Ident = 0
Station_Type = 0
FMS_supp = 0
Hardware_Release = "08"
Software_Release = "B3"
9.6_supp = 1
19.2_supp = 1
93.75_supp = 1
187.5_supp = 1
500_supp = 1
1.5M_supp = 1
3M_supp = 1
6M_supp = 1
12M_supp = 1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 350
MaxTsdr_12M = 550
Redundancy = 0
Repeater_Ctrl_Sig = 0
24V_Pins = 0
Implementation_Type = "SPC3"
Bitmap_Device = "Ip"
;
;-------------------- DP-Slave -----------------------
;
Freeze_Mode_supp = 1
Sync_Mode_supp = 1
Auto_Baud_supp = 1
Set_Slave_Add_supp = 0
Min_Slave_Intervall = 1
Modular_Station = 1
Max_Module = 1
Max_Input_Len = 128
Max_Output_Len = 128
Max_Data_Len = 256
Fail_Safe = 1
Max_Diag_Data_Len = 64
Slave_Family = 3
;
;---------------------- DPV1 -------------------------
;
;
;------------------- UserPrmData ---------------------
;
Max_User_Prm_Data_Len = 15
Ext_User_Prm_Data_Const(0) = 0x00
Ext_User_Prm_Data_Const(1) = 0x00
Ext_User_Prm_Data_Const(2) = 0x08
Ext_User_Prm_Data_Const(3) = 0x00
Ext_User_Prm_Data_Const(4) = 0x00
Ext_User_Prm_Data_Const(5) = 0x00
Ext_User_Prm_Data_Const(6) = 0x00
Ext_User_Prm_Data_Const(7) = 0x40
Ext_User_Prm_Data_Const(8) = 0x00
Ext_User_Prm_Data_Const(9) = 0x63
Ext_User_Prm_Data_Ref(9) = 86
Ext_User_Prm_Data_Ref(9) = 12
Ext_User_Prm_Data_Const(10) = 0x00
Ext_User_Prm_Data_Ref(10) = 13
Ext_User_Prm_Data_Const(11) = 0x40
Ext_User_Prm_Data_Const(12) = 0x00
Ext_User_Prm_Data_Const(13) = 0x00,0x00
;
;-------------------- Modules ------------------------
;
Module = "IP23xx-B310 4 Bit dig. In-Out" 0x30
159
EndModule
Module = "IP24xx-B310 8 Bit dig. In-Out" 0x30
160
EndModule